Skip to content

Lutron RF Contact Closure Output Module

by Lutron
SKU LMK-CCO1-24-B
Original price €140.00 - Original price €140.00 excl. VAT
€172.20 - €172.20 incl. IE VAT
Original price €140.00 excl. VAT
€172.20 incl. IE VAT
€140.00 - €140.00 excl. VAT
€172.20 - €172.20 incl. IE VAT
Current price € via quote
Availability: With lead time Lead times are estimates and will be confirmed with the supplier upon ordering. Our sales team will provide you with the actual lead time as soon as it is received.

Don't worry - the price isn't a secret, we're just required* to share it with you directly. Click 'Request a quote' and we'll get right back to you.

*This may be because products require customisation or professional installation services (which we provide), or are restricted from online sale.

The Lutron RF CCO Module is a low-voltage radio frequency (RF) control that provides a single dry contact closure output. It is designed to integrate with Lutron's RadioRA 2 and HomeWorks QS systems. Powered by either 24 V~ or 24 V-, this module is suitable for building management, HVAC, VAV, and other third-party systems.

Key Features

  • Single contact closure output with normally open (NO) and normally closed (NC) dry contacts
  • Maintained or momentary output type
  • Operates at 24 V~ or 24 V-
  • Utilizes Lutron Clear Connect RF Technology for reliable wireless communication
  • Screw tabs provided for surface mounting or electrical junction box mounting through a 1/2 in or 21 mm trade size knockout opening
  • Complies with NECR 2011 300.22(C)(3) plenum requirements (LMJ- model only)

Specifications:

  • Model Numbers: LMK-CCO1-24-B (Europe, U.A.E.)
  • Operating Voltage: 24 V~ or 24 V-
  • Frequency Bands: 868.125 – 868.850 MHz (LMK-CCO1-24-B)
  • Power Consumption: < 1.0 W
  • Regulatory Approvals: CE, TRA, CITC (LMK- model)
  • Environment: Indoor use, ambient operating temperature 32°F to 131°F (0°C to 55°C), humidity 0% to 90%, non-condensing

Installation and Mounting

  • Screw tabs for surface mounting (recommended) or mounting to an electrical junction box
  • CCO terminals accept 20 to 16 AWG (0.5 to 1.5 mm2) solid or stranded wire

Contact Closure Output

  • Accepts input voltages of 0 to 24 V~ / 0 to 24 V-
  • Resistive Load: 1.0 A (0 to 24 V-), 0.5 A (0 to 24 V~)
  • Provides both normally open (NO) and normally closed (NC) dry contacts
  • Output type: Maintained or momentary
  • Minimum Close Time: 500 ms

WARNING: These controls should only be used to control equipment visible from every control location to avoid entrapment hazards and fire risks. Examples of equipment that must not be operated by these controls include (but are not limited to) motorized gates, garage doors, industrial doors, microwave ovens, heating pads, fireplaces, and space heaters. Ensure that only suitable equipment is connected to these controls.